Long Name: | bay_location |
Applies to: |
|
Description: |
This is the location that the picker moves to initially when going to pick a plate. This should place the 'Bay' sensor on the picker H/A board over the bay tab, about 5mm from the back of the tab. To change the value enter the command as "SET BAY # LOC ##" where # is the bay number and ## is the new location position. Approximate bay positions for 3244 are: Bay 1 = 1030. Bay 2 = 1560. Bay 3 = 2100. Bay 4 = 2630. |
Type: | real |
Default: |
|
Range: |
|
Notes: |
If the picker ends up beyond (aft of) the tab, the firmware will move the picker forward by bay_tab_search_y (alpos btsy) to over the tab then move back till just clear the bay tab (plus an inch of latency) |
Partition: | cal |
See Also: |
|
Go to CTP Firmware NVS Parameter Index Page
Go to CTP Firmware NVS Parameter Search Page