Chiller description and precautions for Magnus 400
The Magnus 400 chiller is a complete unit with no FRU components.
The following types of chillers are available for Magnus 400 and Magnus 400
Xpose:
50 Hz chiller - P/N 370-00003
60 Hz chiller - P/N 370-00004
Precautions:
Temperature control buttonsthe correct temperature of the chiller
water is preset. There is no need to touch the temperature control buttons.
Caution: Changing the temperature control settings
could lead to a malfunction of the chiller and eventual ruin of the
LDA head.
Temperature indicatorthe upper red reading on the temperature
must be between 18.8 and 20.2° C.
Higher or lower temperature readings indicate a malfunction. (Refer to the
Troubleshooting page.)
Flow meterthe flow meter is closed and does not require any
adjustments.
Coolant containerthe cover must be closed at all times, except
when filling coolant.
Air ventsthe air outlet and inlet vents must remain open. Do
not operate the chiller if these vents are blocked.
Flow tubesdo not operate the chiller if the flow tubes are
not connected.
InstallationIf the chiller was not shipped in an upright position,
it takes three hours for the oil in the compressor to settle. Therefor, after
installing the chiller, make sure that the chiller has been in an upright
position for three hours before you connect the Magnus 400 to the power
source.
Lifting the chillerdo not lift use the flow meter as a handle.
Caution: Using the flow meter as a handle when
lifting the chiller could cause the flow meter to break.